inverter will shut down the generator set.
See PMA information in section 49 for engine
speed calculation.
3. Faulty inverter.
CAUTION
Always perform stator check before
replacing the invertor. Failure to do so will result
in damage to the inverter.
Diagnosis/Repair:
1. Contact an authorized Cummins Onan dealer.
CAUTION
Always perform stator check before
replacing the invertor. Failure to do so will result
in damage to the inverter.
OVER TEMPERATURE (INVERTER)
Possible Cause Inverter temperature detected to
be over 70° C.
Diagnosis/Repair:
1. Reduce loads.
CAUTION
Always perform stator check before
replacing the invertor. Failure to do so will result
in damage to the inverter.
OVERLOAD
Possible Cause Too many applications are con-
nected, or the inverter is defective.
Diagnosis/Repair:
1. Measure current draw. If it is greater than 32
amps, reduce the number of appliances con-
nected in the coach and wait a few minutes for
generator set to cool down. Press STOP to stop
engine and restart the generator set.
2. If the generator set shuts down on ’Overload’
condition, disconnect it from the coach and
bench-test with a load-bank. If the generator
set runs fine without shutting down, then the
problem likely exists within vehicle wiring and/
or appliances. In the event that it shuts down
with no load connected, perform checks in Step
3.
3. Ensure stator is not damaged and has no
shorts internally or to Ground on all Main and
Auxiliary Windings. Test winding insulation re-
sistance with a Megger. Replace state if neces-
sary. If the stator is good, replace the inverter.
CAUTION
Always perform stator check before
replacing the invertor. Failure to do so will result
in damage to the inverter.
LOW ENGINE POWER
Possible Cause Engine speed is below 2300 rpm
Diagnosis/Repair:
1. Contact an authorized Cummins Onan dealer.
SYMPTOM DIAGNOSTICS
DEAD OPERATOR PANEL
Possible Cause/Diagnosis/Repair
1. Contact an authorized Cummins Onan dealer.
A. Replace the 30 amp fuse on the internal
control panel, if blown.
B. Check for 12 VDC at Pin 3 of the 10-pin
connector on the internal control panel and
for a good ground at Pin 10.
C. Check for 12 VDC at Pins 2, 3 and 6 of the
9-pin connector on the internal control
panel and for a good ground at Pin 5 of the
6-pin connector.
D. Repair wiring and connectors as neces-
sary.
ENGINE CRANKS BUT DOES NOT START
Note: The generator will make up to three start at-
tempts, cranking each time for 5 seconds and paus-
ing for 2 seconds if necessary before the next crank.
Gen Wait should appear on the display.
Possible Cause/Diagnosis/Repair
1. Clear the Gen Wait message from the Operator
Panel by cycling it off and on. Try starting again.
2. Check the fuel level and fill as necessary.
3. Press the stop switch (p. 2-2) if it is not in its “1”
position.
4. Replace the fuel if it is not of the specified grade
or suitable for the ambient temperature (p 2-1).
ENGINE SPITS/SPUTTERS/EXHAUSTS WHITE
SMOKE
Possible Cause/Diagnosis/Repair
1. Air in fuel system: Prime fuel system by turning
on the display, lift pump should run for 5 min-
utes to prime system. If problem goes away
Zobrazit stránku 28